PART 1 GENERAL
1.1 DESCRIPTION
.1 Work
included: The work described
in this section includes the supply and installation of the Exterior
Insulation and Finish System, as indicated on the drawings and as
specified.
.2
Related Work Under Other Sections:
STEEL STUDS AND FURRING:
Section ___________________________
EXTERIOR GYPSUM SHEATHING BOARD:
Section ___________________________
SEALANTS:
Section: __________________________
(See Note 3.)
1.2 QUALIFICATIONS
.1 The Exterior Insulation and Finish
System shall be installed by a contractor approved and certified
by the system manufacturer. Certification must be in force at the
time the project is bid and contracted for.
1.3 SUBMITTALS
.1 Submit to the architect, for approval,
duplicate samples of Finish Coating colour and texture selected
by the architect. Samples shall be made by applicator utilizing
tools, materials, and techniques proposed for installation.
.2 Obtain architect?s approval of samples
before ordering materials and proceeding with work.
1.4 PRODUCT DELIVERY, STORAGE AND
HANDLING
.1 Store packaged materials in original
containers with manufacturers seals and labels intact, with each
production lot identified by batch number. All lots with same batch
number shall be stored together.
.2 Prevent damage to materials during
handling and storage. Keep materials under cover and free from dampness.
.3 Store products in a cool dry place
out of direct sunlight, protected from the elements and from damage.
.4 System materials shall be stored
at a temperature of not less than 5°C
(40°F).
1.5 JOB CONDITIONS
.1 Ambient temperature must be no less
than 5°C
(40°F)
during installation and until the Adhesive and coatings are dry.
(Minimum 24 hours).
.2 Construct proper free standing scaffolds
460mm (18") from the wall surface to allow continuous uninterrupted
application.
1.6 PROTECTION
.1 Protect adjacent areas from damage
resulting from the installation of the system. All finish work shall
be protected at the end of the day or completion of a section.
.2 Sections of the work must be protected
from adverse weather conditions during the application and until
the coatings are dry.
PART 2 PRODUCTS
2.1 MATERIALS
.1 Exterior
Insulation and Finish System:
The system shall be as manufactured and supplied by Preswitt Manufacturing
Ltd., and comprised of Insulation Board, Sturdy Basecoat Compound,
Reinforcing Fabric and Finish Coating.
.2 Insulation
Boards: Shall be Dow Styrofoam
SM conforming to CGSB Specification 51-GP-20M Type 4. Edges of the
board must be square cut. Maximum width and length of the board
shall be 600 x 2400mm (2' x 8').
Thickness: ________________________
(Specify as required for thermal
resistance).
.3 Sturdy
Compound: Shall be Preswitt
Sturdy Compound.
.4 Reinforcing
Fabric: Shall be a balanced,
openweave glassfiber fabric treated for compatibility with the system
materials. Fabric shall be supplied by Preswitt Manufacturing Ltd.
.5 Mechanical fasteners shall be supplied
by Preswitt of a type and at spacing to suit the project requirements.
.6 Glass
Strands: Loose fill chopped
glass, fiber strands supplied by Preswitt.
.7 Portland
Cement: Type 10 Normal Portland
cement conforming to CSA A5-1977 or Type 1,1-11, or 11 meeting ASTM
C150.
.8 Finish
Coating: Shall be Preswitt
Quality Finish. Colours shall be as selected by the architect from
the manufacturer's standard colour range; custom colours are available
on request.
colour ____________________________
Texture ___________________________
(Select fine, medium or coarse texture
from Manufacturer's standard texture chart).
.9 Metal or vinyl expansion joints,
corner bead, trim etc. shall be to manufacturer's specification.
2.2 MIXING AND PREPARATION
.1 Basecoat:
Drill Sturdy Compound and add Glassfiber strands. Add 10 Kg of Portland
cement gradually to 24 Kg pail of Sturdy Compound and mix. Add a
small quantity of water to improve workability.
.2 Quality
Finish: Drill-mix the material
before applying to the wall surface.
PART 3 EXECUTION
3.1 INSPECTION
.1 Before commencing ensure that environmental
and site conditions are suitable for the installation of the system.
.2 All areas should be even and free
from surface irregularities.
.3 The substrate shall be a type approved
by Preswitt Manufacturing Ltd.
.4 Where exterior gypsum sheathing
is the specified substrate, ensure that it meets the required standard,
is clean, dry, properly fastened and shows no sign of deterioration
or defects.
.5 Wall surfaces shall be sound.
Any discrepancies shall be reported
to the architect or general contractor, and rectified before the
work proceeds. Commencement of work indicates acceptance of conditions.
3.2 INSTALLATION
.1 Starting from a level baseline install
the Insulation Boards in a running bond pattern with the long dimension
applied horizontally. Tightly butt joints of boards. Initial tack
fasten the board to the substrate or framing, using a minimum of
3 fasteners per board. Interlock boards at corners. Ensure that
all adjacent boards are flush at joints: rasp if necessary. The
installed insulated wall surface should be sound, flat and level
in all directions.
.2 The Fiber Mesh reinforcing shall
be applied mechanically over the Insulation Boards with fasteners
spaced 12" o/c vertically and at 16" or 24" to stud
framing. In the case of a solid substrate (e.g. concrete, masonry)
the minimum spacing shall be 12" o/c vertically and 24"
o/c horizontally.
.3 Install specified trim using longest
practical lengths; straight, true and plumb. Corner beads shall
be installed at all vertical external and all salient corners. Secure
all ends and at not more than 12" o/c staggered.
.4 Control joints shall be installed
at locations indicated. If not indicated control joints will be
provided as follows:
a. At suspended soffits when any
one dimension exceeds 4500mm (15') control joints will be provided
at not more than 3000mm(10') on centre.
b. On walls where length of finished
surface exceeds 4500mm vertical control joints will be installed
at 3000mm (10') on centre.
.5 Trowel apply the polymer-modified,
cementitious, Glassfiber Reinforced Basecoat over the Reinforcing
Mesh to a 3-5mm (1/8" to 3/16") thickness. No mesh shall
be visible on the finished surface which shall be left flat and
even in all directions with no high points to receive the Finish
Coat.
.6 Apply finish coating with a steel
trowel and obtain texture by use of a plastic trowel. Coverage shall
be in accordance with the manufacturer's instructions.
.7 Installation of the Exterior Insulation
Finish System shall be done in strict accordance with the contract
documents, and the manufacturer's written instructions. The finished
work shall match approved samples, be uniform in colour, texture
and be free from defects detrimental to appearance and performance.
SPECIFICATION NOTES
1. This guide specification is basic
and must be adapted to suit the requirements of individual projects.
Consult the manufacturer for specific recommendations.
2. This guide specification is prepared
in accordance with Construction Specifications three part section
format and should be included under Division 7 - Thermal and Moisture
Protection as Section 07240, in accordance with CSC/CSI Master Format
for specifications.
3. Insert list of related work specified
in other Divisions, such as steel studs, exterior gypsum sheathing,
sealants, flashings, etc. Sealant compounds should be compatible
with Preswitt Wall System components. Insert also the appropriate
section number.
|